Chilled water flow measurement techniques for chillers
Have you ever wondered how to measure and judge the flow rate of the chiller when you purchased the chiller? Today, the editor brings you the techniques for measuring the flow of chilled water in the chiller, and I hope it will help you.
1. The return water temperature and outlet water temperature detection of the chiller (the unit needs to be in normal state)
After 30 minutes of starting up, check the system or the chilled water system inlet and outlet thermometers through the unit's control system parameters. The inlet and outlet water temperatures of the unit can be read during operation. The difference must be around 4-6 degrees. If the water temperature difference is too large, it means that the water flow of the water system through the plate is too small, which may cause the unit to fail to operate normally or be damaged.
2, water pressure detection of the unit inlet and outlet pipes
Through the detection of the return water pressure and the outlet water pressure value, check the water flow rate of the chiller under the pressure difference between the inlet and outlet water in the random manual of the unit. By referring to the water flow corresponding table or diagram of the unit in the manual, In order to judge whether the water system is normal or not; and through this difference to determine which section of the water pipeline has a large resistance value, and make corresponding rectification plans and actions.
3, the compressor copper pipe suction temperature detection (only detect when the cooling operation
If the suction temperature of the compressor is detected to be lower than 0 degrees after the refrigeration chiller is turned on for 30 minutes, it means that the water flow in the water-side heat exchanger is not enough, which causes the evaporating temperature and evaporating pressure to drop, and causes the Freon to be in the evaporator. The suction pipe flowing to the compressor is still evaporating and absorbing heat, which will cause the compressor suction temperature to be lower than 0 degrees; in addition, it is necessary to exclude the drop in evaporating pressure and evaporating temperature caused by the too low water temperature set point; The standard low water temperature unit can be regarded as normal as long as the compressor has a suction superheat of 6~8℃. Therefore, under normal water flow, the suction temperature of the compressor will generally be greater than 0°C, and water system problems should be eliminated if it is lower than this value.
4, water pump running current detection
By detecting the running current of the chiller pump and comparing it with the rated current, it can be judged whether the actual water flow is larger or smaller than the rated water flow of the pump. Only by comprehensively judging with the previous parameters can an accurate water system detection analysis be obtained. Judgment report.

Related Info
Air conditioner knowledge these 23 application skills you should know Analysis of performance factors of screw chiller assembly accessories Brief analysis case of fan coil selection and layout in central air conditioning Calculation method of power cord size of industrial chiller Causes and elimination of air intake in the refrigeration system of industrial chillersChilled water flow measurement techniques for chillers
Subscribe to relevant news content?
Subscription
Unsubscription
Recent related posts
Customers frequently viewed
IWAYA DENKI Water Pump 25CJT0752
US$2307.69
Panasonic Servo Motor MHMF022L1V2M
US$653.85
Honeywell Solenoid Valve VE4025B1045
US$334.62
ROTEN Mechanical Seal 8E5K-22-X
US$384.62
Copeland Compressor ZPD103KCE-TF5-550
Contact Us
LG LS Contactor 1250023700 GMC-12 AC220V
Contact Us
Rexroth Check Valve SV10GB1-43
Contact Us
Bristol Compressor H21R583CBCR
Contact Us
Balluff Sensor BES02EK
US$241.54
Copeland Compressor 6DS3-400E-TSE-200
Contact Us
OMRON Relay G6EK-134P-ST-US-DC24
US$26.15
Mean Well Power Supply HLG-120H-12B
US$75.73
Ebmpapst Fan G2E140-AL40-01
US$335.70