What if the central air conditioner leaks for no reason
Why does the central air conditioner leak? Is it a defect in the central air conditioner design itself, a loophole in the installation process, or improper use? Let’s break it down in detail below.
The main reasons for the leakage of central air conditioning are as follows:
1. The copper pipe insulation cotton is not wrapped
The indoor pipelines of household central air-conditioning are all made of copper pipes. The temperature of the refrigerant in the copper pipes is very low. If the insulation cotton is not tightly wrapped, or the quality of the insulation cotton does not provide good insulation, the pipeline will A lot of condensed water condensed and dripped down, soaking the ceiling.
Solution: It is recommended to choose some better quality insulation cotton. Copper pipes with different pipe diameters should use insulation cotton with corresponding aperture. When wrapping insulation cotton, be careful not to leave any gap between the insulation cotton and the copper pipe, and ensure that the copper There won’t be any nudity.
2, the drain pipe is not properly connected to the indoor unit
The drain pipe is mainly used for the condensate discharge of the indoor unit. When it is connected to the indoor unit, it uses a flexible connection and needs to be clamped by a clamp. If the connection is not tight, the condensate water will flow out of the gap.
Solution: After connecting the indoor unit and the drain pipe, perform a drainage experiment to ensure that the connection is tight and no water leakage.
3. Poor drainage of condensate
The condensate drain of the indoor unit is blocked or the slope of the drain pipe is not enough, which will cause the condensate to drain well and accumulate on the indoor unit's drain pan. When the drain pan is full, it will overflow and wet the ceiling.
Solution: During construction, make sure that the condensate drain slope cannot be lower than 1/100. Before connecting the drain pipe to the indoor unit, check whether the drain port of the indoor unit is dirty or blocked. The drain pipe must be filled with water after the construction is completed. Experiment to ensure that the condensed water can be discharged smoothly.
4, the drain pipe is not insulated
The temperature of the condensate flowing through the condensate drain pipe is relatively low, so it is necessary to pack insulation cotton during construction. In order to save costs, some engineering companies did not wrap the condensate drain pipe with thermal insulation cotton, resulting in condensate on the outer wall of the drain pipe. Condensation, causing water leakage.
Solution: All condensate drain pipes must be covered with thermal insulation cotton, and the standards and requirements for thermal insulation cotton are the same as those for copper pipes.
In addition, the following points should be paid attention to when installing central air conditioners:
1. The installation position of the air conditioner must be safe, stable, convenient for maintenance, and well ventilated.
2. Different fixing materials should be used to fix the air conditioner according to various wall structures.
3. The mounting bracket of the air conditioner must meet the requirements of relevant national laws and regulations, and have sufficient strength, rust and corrosion resistance. At the same time, the size of the mounting bracket matches the size of the footing of the outdoor unit.
4. It is recommended to use expansion bolts to fix; when the strength of the installation surface is insufficient, corresponding reinforcement, support or shock absorption measures should be taken to prevent the normal operation of the air conditioner from being affected or causing danger.
5. The horizontal installation of the indoor unit should be controlled within ±1°, otherwise it is easy to cause problems such as poor drainage.
6. Pay attention to dust protection when installing the engineering machine.

Related Info
Use and principle of inverter air conditioner and ordinary air conditioner What are the characteristics of lithium bromide absorption refrigeration units in air conditioning projects What are the classifications of air conditioning refrigerants What are the consequences of the trend of piston refrigeration compressors What are the tips for purchasing a screw chiller for the first timeWhat if the central air conditioner leaks for no reason
Subscribe to relevant news content?
Subscription
Unsubscription
Recent related posts
Customers frequently viewed
IWAYA DENKI Water Pump 25CJT0752
US$2307.69
Panasonic Servo Motor MHMF022L1V2M
US$653.85
Honeywell Solenoid Valve VE4025B1045
US$334.62
ROTEN Mechanical Seal 8E5K-22-X
US$384.62
Chint Circuit Breaker NB1L-40/2P
Contact Us
YUKEN Vane Pump PVR50-F-T51-LLL-3180
Contact Us
Copeland Compressor 6DJ3A300E-TSK
Contact Us
ASCO Solenoid Valve SCG552A017MS
Contact Us
Moeller Contactor DILH2000/22(RAW250)
US$25403.46
Ebmpapst Fan G4D200-BL19-03
Contact Us