What are the requirements for the coefficient of performance (COP) of the chiller
Choosing the right chiller needs to focus on understanding the chiller's cooling capacity, chilled water capacity, thermal efficiency, water tank capacity, temperature control accuracy, water quality requirements, and water circulation system material requirements. The following data is the chiller cooling capacity performance coefficient requirement.
1. Piston/scroll chiller, its coefficient of performance (COP) requirements are as follows:
When the rated cooling capacity is less than 528KW, the COP should not be less than 3.8;
When the rated cooling capacity is 528~1163KW, the COP should not be less than 4.0;
When the rated cooling capacity is greater than 1163KW, the COP should not be less than 4.2.
2. For screw chillers, the coefficient of performance (COP) requirements are as follows:
When the rated cooling capacity is less than 528KW, the COP should not be less than 4.10;
When the rated cooling capacity is 528~1163KW, the COP should not be less than 4.30;
When the rated cooling capacity is greater than 1163KW, the COP should not be less than 4.60.
3. For centrifugal chillers, the coefficient of performance (COP) requirements are as follows:
When the rated cooling capacity is less than 528KW, the COP should not be less than 4.40.
When the rated cooling capacity is 528~1163KW, the COP should not be less than 4.70.
When the rated cooling capacity is greater than 1163KW, the COP should not be less than 5.10.
4. For evaporative cooling or air-cooled chillers/piston/scroll chillers, the coefficient of performance (COP) requirements are as follows:
When the rated cooling capacity is less than or equal to 50KW, the COP should not be less than 2.40.
When the rated cooling capacity is greater than 50KW, the COP should not be less than 2.60.
5. For air-cooled or evaporative-cooled screw chillers, the coefficient of performance (COP) requirements are as follows:
When the rated cooling capacity is less than or equal to 50KW, the COP should not be less than 2.60.
When the rated cooling capacity is greater than 50KW, the COP should not be less than 2.80.
6. The requirements for the integrated part-load performance factor (IPLV) of water-cooled screw chillers are as follows:
When the rated cooling capacity is less than 528KW, its IPLV should not be less than 4.47.
When the rated cooling capacity is 528~1163KW, its IPLV should not be less than 4.81.
When the rated cooling capacity is greater than 1163KW, its IPLV should not be less than 5.13.
7. The requirements for the integrated partial load performance factor (IPLV) of centrifugal water-cooled units are as follows:
When the rated cooling capacity is less than 528KW, its IPLV should not be less than 4.49.
When the rated cooling capacity is 528~1163KW, its IPLV should not be less than 4.88.
When the rated cooling capacity is greater than 1163KW, its IPLV should not be less than 5.42.
When the air-cooled unitary unit with a nominal cooling capacity greater than 7.1kW, its energy efficiency ratio requirements are as follows:
When the duct is not connected, the energy efficiency ratio is not less than 2.60.
When is connected to the air duct, the energy efficiency ratio shall not be less than 2.30.
When a water-cooled unitary unit with a nominal cooling capacity greater than 7.1kW, its energy efficiency ratio requirements are as follows:
When the duct is not connected, the energy efficiency ratio is not less than 3.00.
When is connected to the air duct, the energy efficiency ratio shall not be less than 2.70.
1. Use side: refrigeration inlet/outlet water temperature 12/7℃.
2. Heat source side (or heat release side): water-cooled cooling water inlet and outlet temperature is 30/35℃, air-cooled cooling air dry bulb temperature is 35℃, evaporative cooling air wet bulb temperature is 24℃.
3. The fouling coefficient on the use side and the water-cooled heat source side is 0.086m2.℃/kW.

Related Info
The temperature status and failure causes of the unit components of various commercial central air conditioning systems Treatment method for water leakage of central air conditioner Treatment method of ammonia refrigerant in refrigeration equipment Want to clean the air conditioner condenser Come here i teach you What are the common problems in the use of cold storage for preservation productsWhat are the requirements for the coefficient of performance (COP) of the chiller
Subscribe to relevant news content?
Subscription
Unsubscription
Recent related posts
Customers frequently viewed
IWAYA DENKI Water Pump 25CJT0752
US$2307.69
Panasonic Servo Motor MHMF022L1V2M
US$653.85
Honeywell Solenoid Valve VE4025B1045
US$334.62
ROTEN Mechanical Seal 8E5K-22-X
US$384.62
Sanyo Denki Servo Motor DD045MB064A00
Contact Us
Bristol Compressor H2EB323ABCE
Contact Us
Fuji VFD Frequency Converter FRN2.2F1E-2U
Contact Us
SKF Bearing 23148 CC/W33
US$1461.54
JAMICON Fan KF0410B2HS-R
US$5.77
Emerson Alco Expansion Valve TX3-Z37 801947M
Contact Us
Sanyo Denki Servo Drive PQM1A050HF66S3N
US$192.31
Suntronix Fan SG146HA2
US$210.77