The design points of capillary refrigeration system
1. On the high-pressure side of the refrigeration system, do not install a liquid reservoir, and try to reduce its effective volume on the premise that the condenser can contain all the refrigerant.
Because in a refrigeration system that uses capillary tubes as throttling elements, if the accumulator or condenser is too large, when the compressor stops, the refrigerant liquid will continue to flow to the evaporator. In severe cases, the liquid in the evaporator will be absorbed by the compressor. Inhaled when restarting, it is easy to produce liquid hammer and damage the compressor.
2. The refrigerant injected into the tank in the refrigeration system should be appropriate and accurate to match the capacity of the evaporator. Because the amount of refrigerant in the tank is too much or too little, it will affect the cooling capacity of its refrigeration system. The tank charge of the refrigerant in the general refrigeration system is determined by experiment after design calculation.
3. When the capillary is selected, its inner diameter and length should have a certain ratio.
If the capillary tube is too short, its flow resistance is small, the flow rate is large, and hot steam is easily mixed into the capillary tube, thereby reducing the refrigeration efficiency, and it is also easy to cause the liquid to return to the compressor and cause liquid hammer; if the capillary tube is too long, its flow resistance Large, causing the exhaust pressure to be too high, and the amount of liquid entering the evaporator is insufficient, causing the suction pressure to be too low. According to some information, under the same working condition and the same flow rate, the length of the capillary tube is approximately proportional to the 4.6th power of its inner diameter, that is, L1/L2=(D1/D2)4.6.
4. Appropriately increase the effective volume of the evaporator.
In a refrigeration system that uses capillary tubes as throttling elements, appropriately increasing the effective volume of the evaporator can not only prevent the liquid from returning to the compressor and cause liquid hammer, but also reduce the equilibrium pressure when the compressor is stopped, and reduce its Start load.
5. The refrigeration system should be kept clean and dry to avoid the entry of water or impurities.
Because the inner diameter of the capillary is small, the entry of water or impurities can easily cause ice blockage or dirty blockage. The components in its refrigeration system have requirements for moisture content and impurity content, and a filter drier is installed at the capillary inlet. In actual products, because of cost considerations, desiccants are rarely used in small systems, and only very cheap filters are used.

Related Info
Six common problems of central air conditioning Standard Design and Installation Specification for Cold Storage Ten matters needing attention in the use of liquid nitrogen tanks The cold water (freezing) machine displays the reverse phase loss fault quick troubleshooting The cooling effect of industrial chillers is getting worse You may have forgotten this operationThe design points of capillary refrigeration system
Subscribe to relevant news content?
Subscription
Unsubscription
Recent related posts
Customers frequently viewed
IWAYA DENKI Water Pump 25CJT0752
US$2307.69
Panasonic Servo Motor MHMF022L1V2M
US$653.85
Honeywell Solenoid Valve VE4025B1045
US$334.62
ROTEN Mechanical Seal 8E5K-22-X
US$384.62
Banner Sensor S18-2NAEL-9M
US$46.15
Sanyo Denki Fan 109X6512A1046
US$12.32
Baumer Sensor IGYX 18P17E3/L
Contact Us
Meas Transmitter M5156-000002-016BG
US$253.91
ENC VFD Frequency Converter EN600-7T2000P
Contact Us
Festo Sensor SDE1-D10-G2-MS4-L-P2-M12
US$575.00
Mitsubishi Compressor TNB220FMCH
US$423.08