Failure Analysis of Air Conditioner Button Circuit
Where is the button circuit in the inverter air conditioner? The first is the function keys on the display board, and the second is the automatic switch on the main board. The main purpose is to transmit user instructions and achieve the purpose of information interaction. So, how does it work? What are the common after-sales failures? This article is through the analysis of the circuit, hoping to give you some help in the after-sales maintenance.
 
   1. Circuit principle
 
When the button is off, there is no loop on the circuit, and the single-chip microcomputer is in a high level state; when the button is pressed on, the 5v direct current is connected to the power ground through R1, forming a loop, and the PIN port is in a low level state. . In this way, the microcomputer can receive the user's button information. Some use membrane buttons, the upper and lower membranes are coated with conductive rubber circuits, and there is a membrane in the middle with holes to isolate the two membranes with conductive rubber. The button is in the position of the hole. When the button is pressed, two films with conductive rubber pass through the round hole in the middle, connect the circuit, and output through the chip code.
 
   2. Common faults
 
  Case number one
 
   Fault phenomenon: A wall-mounted air conditioner automatically restarts after being used for a period of time.
 
   Reason analysis: There are three situations for automatic reset, the first is that the first is too low; the second is electromagnetic interference; the third reset button circuit is faulty.
 
  Troubleshooting: Check the power supply and find no abnormalities; check the surroundings and find no sources of electromagnetic interference. After checking the automatic switch, it was found that it was in the joint state, and the switch was mainly connected to the reset circuit of the single-chip microcomputer. After further analysis, it was found that the switch had silver ion migration.
 
  Case 2
 
  Fault phenomenon: A 2-hp cabinet machine has a button failure fault.
 
  Cause analysis: General inspection found that the button failed but the display was normal, so the power supply should be normal. Further inspection found that the button was corroded and broken.
 
   Troubleshooting: Replace button
   Three, additional knowledge points
 
   1. In order to avoid accelerating the generation of electromigration, the manufacturer will set the effective time of the automatic button as 5 minutes after power-on, after which the button will be invalid.
 
  2. After-sales maintenance can judge the type of problem according to the phenomenon, for example, the reset phenomenon is an automatic button, and the display panel button is abnormal when the function is abnormal.
 
   3. Some buttons are dirty, which can be cleaned with alcohol, or foreign objects can also be cleaned.

Related Info
What are the specific operation methods for maintenance of screw compressors in cold storage Key points for safe operation of refrigeration operators in large cold storage What to do if the compressor of screw chiller is damaged Refrigeration principles of refrigerators and air conditioners Common problems and solutions of industrial chillers summarized by the maintenance masterFailure Analysis of Air Conditioner Button Circuit
Subscribe to relevant news content? 
Subscription
 Unsubscription
Recent related posts
Customers frequently viewed
IWAYA DENKI Water Pump 25CJT0752
US$2307.69
 Panasonic Servo Motor MHMF022L1V2M
US$653.85
 Honeywell Solenoid Valve VE4025B1045
US$334.62
 ROTEN Mechanical Seal 8E5K-22-X
US$384.62
 Daikin Solenoid Valve KSO-G02-4BC-20-EN
Contact Us
 Parker Servo Drive ZXF600-DRIVE-240V
US$4113.00
 Festo Sensor SPABT-B2-R18-2N-K1-SA
Contact Us
 BRIDGE Welding Wire TGF-308
US$19.23
 Copeland Compressor ZPU870KWE-TEP-600
Contact Us
 Copeland Compressor RFT29C1E-CAA-182
Contact Us
 Autonics Rotary Encoder E40HB6-2048-2-V-24
US$1153.85
 Emerson Alco Expansion Valve BAE2/3ZW195
US$142.69
 Suntronix Fan SJ15050HA2
US$61.54