The detection of the power supply voltage of the chiller
Industrial chiller units are widely used. Where there is industry, chiller equipment is required, such as: chemical chillers, electroplating chillers, food chillers, electronic processing chillers, mold chillers, printing chillers, etc., and large Some industries have high requirements for industrial chillers, and most customers require 24-hour operation, so the power supply voltage requirements for chillers are also very high. If the voltage imbalance of several phases of the chiller is too 2%, operation It may damage the chiller from time to time, so control the chiller well.
Chiller power supply voltage detection
If the standard voltage of the chiller is 3-phase, 380V, 50Hz, the measured UAB=376V, UAC=379V, UBC=385V. Get the average voltage=(376+379+385)/3=380V: Determine the deviation from the average voltage: △UAB=380-376=4V, △UAC=380-379=1V, △UBC=385-380= 5V, the maximum deviation is 5V, 5/380=1.3%, and the maximum phase voltage unbalance is 1.3%.
If the power supply and voltage are measured within the normal range, it can start normally. If the chiller's power supply is not well controlled, then there will be a high maintenance cost if it is damaged. Normally, the voltage will be relatively normal.
The maximum allowable phase voltage imbalance of the power supply voltage of the chiller is 2%, and the phase current imbalance is 10%. Note: When the phase voltage unbalance is greater than 2%, it must not be switched on.
The working power supply of the chiller is 3-phase, 380V, 50Hz. Before running the chiller, you need to check whether the power supply and control parts in the electric control cabinet are abnormal, and tighten the wiring terminals, including the main power wiring copper bar, automatic air circuit breaker (air switch), Δ-Δ or Y-Δ Compressor start electrical device, PLC touch screen, target flow switch, chilled water pump, cooling water pump linkage control line (control contact is passive contact), temperature sensor, freezing, cooling water pump, cooling water tower linkage control line (control contact is passive contact ), electronic control instruments and other nodes. After confirmation, the startup operation can be performed to ensure the normal operation of the chiller.
The chiller is a high-power machine, and the voltage is basically industrial voltage, 380V, so it is best to install a voltage stabilizer when installing the chiller.

Related Info
Reasons for internal protection of industrial chiller compressors Selection requirements for cold storage refrigerants Several details in the cold storage installation process Specification for selection and installation of refrigeration piping parts for chillers The correct way to open the refrigerated truck for summer maintenanceThe detection of the power supply voltage of the chiller
Subscribe to relevant news content?
Subscription
Unsubscription
Recent related posts
Customers frequently viewed
IWAYA DENKI Water Pump 25CJT0752
US$2307.69
Panasonic Servo Motor MHMF022L1V2M
US$653.85
Honeywell Solenoid Valve VE4025B1045
US$334.62
ROTEN Mechanical Seal 8E5K-22-X
US$384.62
EACO Capacitor STM 700V 3.3UF
US$2.31
Copeland Compressor 6MJD-45X-EWL
Contact Us
FAG Bearing 30315-A
US$300.00
VBI Bearing 6219-ZZ
US$45.38
HENGSTLER Encoder AC58/0013EK.42SBC
US$613.72
COSEL Power Supply ADA600F-24-FW
US$1348.85
Ebmpapst Fan VBS0101XUGDS
Contact Us