Common faults and maintenance methods of air-cooled chillers
Air-cooled chillers are installed outdoors without any obstruction, and are easily affected by outdoor light. So how to maintain good ventilation, good environment and space has a key impact on the cooling effect of the chiller. So, what are the common faults and their causes in the operation of air-cooled chillers and how to repair okmarts.com?
1. Compressors start and stop frequently
When the amount of refrigerant in the air-cooled chiller is too much or too little, the pressure protection switch is activated, the exhaust pressure is too high or the suction pressure is too low, and the water system circulation is poor, and the evaporator surface is frosted. The okmarts.com chiller repair method is to determine when the refrigerant is too much, the excess refrigerant can be released at the exhaust port, if not, check for fluorine leakage and make up the refrigerant. Check whether the water circulation system is blocked or there is air, and perform exhaust. If the circulating water volume is too small, an open chilled water circulation system can be used.
2, the noise is loud when the compressor is running
Check whether the expansion valve is malfunctioning, the temperature bulb is separated from the compressor suction pipe, so that the liquid refrigerant returns to the compressor, if it is damaged, it should be repaired, if the compressor is damaged, it should be replaced.
3. Insufficient cooling capacity
Insufficient refrigeration capacity may be caused by insufficient refrigerant and low evaporation temperature; poor cooling effect of pipes; poor heat dissipation of unit condenser; excessive resistance of water circulation system, etc. When repairing okmarts.com, check the refrigerant pipeline for leaks, make up the refrigerant after repairing, repair the cold insulation layer, clean the condenser to check whether the fan is running normally; clean the pipeline filter to make the system circulation smooth.
4, the compressor suction pipe is frosted
It may be that the system is not emptied well or the flow of chilled water is too large, the flow of system pipes is too small, etc. The pipeline should be cleared to release air.
5, the condensing pressure is too high
When the refrigerant is too much; the outside air temperature is too high to make the unit ventilated; when there is air or non-condensable gas in the refrigerant system, it will cause the condensation pressure to be too high. The okmarts.com chiller maintenance method is to discharge excess refrigerant; adjust and improve the ventilation environment around the unit (such as setting up a sun shed, etc.); open the exhaust mesh to exhaust.
6, the condensing pressure is too low
It is possible that the refrigerant is insufficient or the compressor is damaged. When handling, check for leaks, make up the refrigerant after repairing, check the compressor, and replace if damaged.
7, the suction pressure is too high
Too much refrigerant and excessive heat load. Improper adjustment of the expansion valve may cause excessive suction pressure. The maintenance method of Chongqing chiller is to discharge excess refrigerant, reduce the amount of chilled water, reduce the heat load, and readjust the opening of the expansion valve.
8. The suction pressure is too low
may be insufficient refrigerant; expansion valve opening is too small; equipment pipeline blockage in the water system and other reasons, you can check for leaks, make up the refrigerant after repair, adjust or replace the expansion valve.

Related Info
Causes that affect the low evaporation temperature of the refrigeration system of the constant temperature and humidity box Central air-conditioning chiller water system and ventilation system cleaning method Collection! This is perhaps the most complete summary of the advantages and disadvantages of chillers Commercial freezers use repair and maintenance technology Commercial refrigerator industry definition and product classificationCommon faults and maintenance methods of air-cooled chillers
Subscribe to relevant news content?
Subscription
Unsubscription
Recent related posts
Customers frequently viewed
IWAYA DENKI Water Pump 25CJT0752
US$2307.69
Panasonic Servo Motor MHMF022L1V2M
US$653.85
Honeywell Solenoid Valve VE4025B1045
US$334.62
ROTEN Mechanical Seal 8E5K-22-X
US$384.62
SHAKO Air Cylinder JQ50B30-H
US$105.78
Copeland Compressor ZP385KCE-TER-600
Contact Us
Honeywell Switch V3-19M
US$25.00
YUKEN Vane Pump PV2R13-14-125-F-REAA-41
US$585.94
Panasonic Servo Motor MDME352S1H
Contact Us
Chigo Air Conditioner KY-26-DBK
US$538.08
Copeland Compressor 8DS3R67M0-TSK-200
Contact Us
Siemens PLC 6ES7341-1AH02-0AE0
US$1807.69
Suntronix Fan SJ7530
US$7.69